Summary

406 - JWG A2/B4.28 monitored the reliability in service of HVDC Converter Transformers and the TB reports, over a period 1971-2009, an encouraging decrease in the failure rate. It also reviewed existing standard test specifications, with a view of representing the real service conditions. The importance of the Polarity Reversal (PR) test and the effect of the oil conductivity and the polarization time are stressed. The conclusion is that at this stage the existing test should not be modified. 407 - A design review provides a common customer-manufacturer understanding of the applicable standards and specification requirements. It is an opportunity to scrutinize the design to ensure the requirements will be met, using the manufacturer's proven materials and methodology. This document prepared by A2/B4.28, is based on the existing guide (TB 204) while expanding to address specific aspects associated with the HVDC Converter Transformer, such as higher harmonic or transient waveforms.