Summary

The minimum flashover voltage, VMF, of a short insulator string of four units of IEEE standard insulators fully bridged with ice in two positions, at a 60° inclined angle and in vertical position, under dc+, dc- and ac test voltage were measured. A notable increase in insulation strength of the inclined position compared to the I-string vertical position under heavy icing conditions was observed. The increase in VMF under dc-voltage were 21% and 39% for applied water conductivities of 100 and 60 µS/cm, respectively. Such increase was also observed for dc+ and ac. Furthermore, this paper reports the processes observed by a high speed camera during arc propagation on the ice-covered inclined insulator.

Additional informations

Publication type ISH Collection
Reference ISH2015_429
Publication year 2015
Publisher ISH
File size 289 KB
Price for non member Free
Price for member Free

Authors

Lühmann Nicole, Bartunková Monika

EXPERIMENTAL INVESTIGATION OF THE PROCESS OF ARC PROPAGATION OVER AN ICE-COVERED INCLINED INSULATOR