Summary

Dissolved Gas Analysis (DGA) is probably the most effective technique applied to transformers for condition monitoring and incipient fault diagnosis. Typical fault gases in transformers are H2, CH4, C2H4, C2H6, C2H2 CO and CO2, and different key gases indicate fault types and amount of fault levels. Recently new inhibited transformer oil is developed based on the latest Gas-to-Liquid (GTL) technology by hydrocracking of waxy hydrocarbons generated from synthesis gas. This oil contains mainly paraffinic (primarily iso-paraffinic) hydrocarbon molecules. DGA characteristics of GTL oil under different fault conditions need to be studied. In this work, a test platform is developed for DGA-thermal fault study, which integrates a multi-gas online DGA monitor, a heating element and a gas tight test cell. GTL oil (Diala S4 ZX-I) is tested under various thermal faults including T1 (< 300 °C), T2 (300 °C – 700 °C) and T3 (> 700 °C) levels. A conventional mineral oil Gemini X is also tested as the benchmark. DGA fingerprints of GTL and Gemini X are obtained under the same fault conditions.

Additional informations

Publication type ISH Collection
Reference ISH2015_424
Publication year 2015
Publisher ISH
File size 482 KB
Price for non member Free
Price for member Free

Authors

Zhang Chongxing, Wiens Christian, Claudi Albert, Guðjónsdóttir, Gora Tatenda, Ye Rixin

Dissolved Gas Analysis of a Gas to Liquid Hydrocarbon Transformer Oil under Thermal Faults
Dissolved Gas Analysis of a Gas to Liquid Hydrocarbon Transformer Oil under Thermal Faults