Summary

In this work is presented in a simulated environment, the analysis of the required length of conterpoise cable connected to the ground rod in a transmission line located in Maceió - AL, capable of avoiding the phenomenon known as back flashover, in other words, the disruptive discharges of return in the chain of insulators when subjected to standardized atmospheric discharges considering some values of soil resistivity and some types of arrangement of geometric arrangements of grounding systems.

Additional informations

Publication type ISH Collection
Reference ISH2017_393
Publication year
Publisher ISH
File size 784 KB
Pages number 6
Price for non member Free
Price for member Free

Authors

LILAND, Oh, MACIELA, VU-CONG, SLAMA

Keywords

Grounding Systems, Distribution Line, Atmospheric Outbreaks, ATPDRAW, voltage surges

Analysis of grounding systems applied to a distribution line of maceió-AL in front of atmospheric outbreaks
Analysis of grounding systems applied to a distribution line of maceió-AL in front of atmospheric outbreaks