Order Publications

Reference: ISH2015_227

Type:
ISH Collection
Title:

Investigation on shielded rooms for reduction of the partial discharge back ground noise level using a new measurement method

 

Abstracts

Shielded rooms are common equipment in high voltage testing laboratories. Especially a low background noise level is required if a low partial discharge level has to be proven for a high voltage equipment in a routine or type test field. Test fields are mostly integrated into the factory of the HV equipment. High voltage tests on HV Cables have the highest requirements on the background noise level of the laboratory. Therefore the effectiveness of the damping is important. According to the IEEE standard 299 or the DIN EN 61587-3 the damping characteristic can be measured. The effective background noise level expressed in PD cannot be predicted. The current paper proposes a measurement method which verifies a very low background noise level caused by radiated interferences. The partial discharge signal consists of a rectangle impulse. The new measurement method takes the rectangle disturbing signal in account. The goal is to ensure a certain background noise level in a shielded room which is integrated in a certain environment of a factory. The new method is demonstrated on a test set up.
 

File Size: 267 KB

Year: 2015

 
 
 
Download
Member
FREE free
Non member
FREE free
 

Your AccountYour Account

Password forgotten

Members

may download free of charge all publications including most recent ones


Non Members

may download free of charge publications over three years old and purchase all publications

ContactContact

For any questions in connection with the on-line library, contact:


Publications and Editions Manager

publications@cigre.org